1. The ratio of the amount of electricity in the cross section of the conductor to the time required to pass the amount of electricity refers to (a)
a, current b, voltage c, resistance d, electrical work
2. The difference between any two potentials in the electric field is (b).
a, resistance b, voltage c, current d, electrical work
3. Rated voltage: The maximum allowable working voltage that the insulating part can withstand for a long time means (c)
a, current b, voltage c, rated voltage d, electrical work
4. The work done by the current means (d)
a, current b, voltage c, resistance d, electrical work
5. The work done by the current per unit time means (d).
a, current b, voltage c, electrical work d, electric power
6. Equipment rated power The power consumed by the electrical equipment when operating at rated voltage is (b).
a, rated voltage b, rated power c, current d, electrical work
7. An alternating current with only one phase of sinusoidal alternating electromotive force is called (a)
a, single-phase AC b, single-phase current c, single-phase voltage d, single-phase resistance
8. An alternating current with a three-phase sinusoidal alternating electromotive force is called (a)
a, three-phase alternating current b, three-phase current c, three-phase voltage d, three-phase resistance
9. The meaning of red in the security color is (a)
a, prohibit / stop b, instructions must comply with the rules c, warning / attention d, prompt security status
10. The meaning of blue in the security color is (b)
a, prohibit / stop b, instructions must comply with the rules c, warning / attention d, prompt security status
11. The meaning of yellow in the safety color is (c)
a, prohibit / stop b, instructions must comply with the rules c, warning / attention d, prompt security status
12. The meaning of green in the safe color is (d)
a, prohibit / stop b, instructions must comply with the rules c, warning / attention d, prompt security status
13. Equipment that must be constantly moved during work, or that does not need to build a special foundation and often change its working place when it is installed (b)
a, hand-held electrical equipment b, mobile electrical equipment c, fixed electrical equipment d, leak detection device
14. Electrical equipment that must be manually held and moved by the mobile device body or work together is (a)
a, hand-held electrical equipment b, mobile electrical equipment c, fixed electrical equipment d, leak detection device
15. Electrical equipment installed on a special basis other than mobile and hand-held is (c)
a, hand-held electrical equipment b, mobile electrical equipment c, fixed electrical equipment d, leak detection device
16. When the leakage current in the power network reaches a dangerous value, the device that can automatically cut off the power supply is (d)
a, hand-held electrical equipment b, mobile electrical equipment c, fixed electrical equipment d, leak detection device
17. The operation of moving (moving) the installation position of the equipment under the charged state is (a)
a, live relocation b, no live relocation c, dangerous operation d, safe operation
18. Compared with general-purpose equipment, general-purpose electrical equipment for mines (abcd) have requirements for adapting to specific conditions of coal mines, and can prevent direct contact and charging of parts from the outside and prevent vertical dripping of water droplets, and creepage distance of terminal blocks and There are special regulations for air gaps.
a, medium temperature b, moisture resistance c, shell material and strength d, line device
19. Explosion-proof electrical equipment specially used for coal mine underground production according to GB3836.1-2000 standard means (d)
a, hand-held electrical equipment b, mobile electrical equipment c, leak detection device d, mine explosion-proof electrical equipment
20. When the power supply voltage is as low as the specified limit value, the relay protection device that can automatically cut off the power supply is (a)
a, under voltage release protection device b, leak detection device c, mobile electrical equipment d, grounding device
21. The total grounding and grounding conductors and grounding leads are collectively referred to as (b)
a, leak detection device b, grounding device c, under voltage release protection device d, incoming line device
22. The grounding poles that are buried separately in a centralized or single location with electrical equipment (including junction boxes that connect the power armored cables) are (a)
a, local grounding pole b, grounding resistance c, incoming line device d, leak detection device
23. In the process of transportation of electric energy from the power plant to the user, power and energy loss will inevitably occur, and the power generated corresponding to this loss is (b)
a, power load b, line loss load c, power supply load d, power load
24. In the classification of electric load, sudden interruption of power supply will result in the greatest loss and damage (a)
a, one type of load b, two types of load c, three types of load d, four types of load
25. In the power load classification, the power supply is suddenly interrupted, and the loss and harm caused by it will be minimal ( c )
a, one type of load b, two types of load c, three types of load d, four types of load
26. The purpose of which type of protection is to prevent the overhead line entering the substation from being subjected to direct lightning strikes in the near area, and to limit the overvoltage value of the lightning intruding wave input from a remote place to a lightning arrester or cable line, series reactor, etc. Smaller values ​​that are not dangerous to electrical equipment. (a)
a, substation line protection
b. Install the valve type arrester on the busbar of the substation
c. Install the valve type arrester at the neutral point of the main transformer
d. Install a valve type arrester at the terminal of the power cable directly connected to the overhead line.
27. What type of short circuit belongs to the following figure ( a )
a, three-phase short circuit b, two-phase short circuit c, two-phase ground short circuit d, single-phase short circuit
28. What type of short circuit belongs to the following figure ( d )
a, three-phase short circuit b, two-phase short circuit c, two-phase ground short circuit d, single-phase short circuit
29. What type of short circuit belongs to the following figure ( b )
a, three-phase short circuit b, two-phase short circuit c, two-phase ground short circuit d, single-phase short circuit
30. What type of short circuit belongs to the following figure ( c )
a, three-phase short circuit b, two-phase short circuit c, two-phase ground short circuit d, single-phase short circuit
31. Thundercloud directly discharges electrical equipment or power lines. When lightning current flows through these devices, an impulse voltage is generated on the impedance of the lightning current flow path (including the grounding resistance), causing an overvoltage. This overvoltage is called (a)
a, direct lightning strike voltage b, lightning strike counter overvoltage
c, inductive lightning overvoltage d, lightning intrusion wave
32. Thundercloud discharges the top of the tower of the power overhead line, or the thundercloud discharges the lightning line at the top of the power overhead linear tower. There is a high potential at the top of the tower. This high potential acts on the wire insulator of the line. If the voltage is high enough, it may cause breakdown and discharge the wire. This condition is called (b).
a, direct lightning strike voltage b, lightning strike counter overvoltage
c, inductive lightning overvoltage d, lightning intrusion wave
33. Lightning occurs not far in the vicinity of electrical equipment (such as overhead power lines). Although lightning does not directly hit the line, a large amount of bound charge opposite to the thundercloud is induced on the wire, forming (c)
a, direct lightning strike voltage b, lightning strike counter overvoltage
c, inductive lightning overvoltage d, lightning intrusion wave
34. A rapidly flowing charge in a transmission line conductor due to a direct lightning strike or an induced lightning strike is called (d)
a, direct lightning strike voltage b, lightning strike counter overvoltage
c, inductive lightning overvoltage d, lightning intrusion wave
35. The overvoltage that is generally caused by an unbalanced fault in the line no-load, single-phase grounding or three-phase system and may last for a long time is (a)
a, power frequency overvoltage b, resonant overvoltage
c, operating over voltage d, inductive lightning overvoltage
36. When the integrated impedance in the circuit is very small, a large current will occur at a low power supply voltage. This extremely large current produces a high voltage drop in the inductor and capacitor, which is (b)
a, power frequency overvoltage b, resonant overvoltage
c, operating over voltage d, inductive lightning overvoltage
37. In the power system, due to operation or accident, the operating state of the equipment changes, and the electric field and magnetic field energy on the capacitance and inductance of the related equipment are mutually converted. The mutual conversion of the electric and magnetic energy may cause the overvoltage generated by the oscillation. (c)
a, power frequency overvoltage b, resonant overvoltage
c, operating over voltage d, inductive lightning overvoltage
38. When a misoperation occurs, a strong arc can cause arc burns, which can cause redness, blistering, tissue scorching, and necrosis. This is the following type of electrical injury (a)
a, electric burn b, electric imprint c, skin metallization d, electric shock
39. The following type of electrical injury occurs at a good contact point between the human body and the charged body (b)
a, electric burn b, electric imprint c, skin metallization d, electric shock
40. The following type of electrical injury is caused by the high temperature arc causing the surrounding metal to melt, evaporate and splash into the skin surface ( c )
a, electric burn b, electric imprint c, skin metallization d, electric shock
41. Among the following current types, the current that can be felt by the human body but not damaged is (a)
a, sense current b, get rid of current c, lethal current d, detection current
42. Among the following current types, the human body can get rid of it after electric shock, and the current with pain and heart rate disorder is (b)
a, sense current b, get rid of current c, lethal current d, detection current
43. Among the following current types, the life-threatening current of the human body after being shocked is (c)
a, sense current b, get rid of current c, lethal current d, detection current
44. The human body is on the ground or other grounding conductor, and an electric shock accident in which a part of the human body touches a phase charged body is (a)
a, single-phase electric shock b, two-phase electric shock c, strid voltage electric shock d, contact voltage electric shock
45. The electric shock accidents of two human bodies touching the two-phase charged body at the same time are (b)
a, single-phase electric shock b, two-phase electric shock c, strid voltage electric shock d, contact voltage electric shock
46. ​​When the charged body has a ground fault, a fault current flows into the earth, and a current voltage drop occurs in the soil around the ground point. When a person is around the grounding point, there is a stride voltage between the two feet, and the electric shock caused by the voltage is (c)
a, single-phase electric shock b, two-phase electric shock c, strid voltage electric shock d, contact voltage electric shock
47. The electric shock caused by the contact voltage is (d)
a, single-phase electric shock b, two-phase electric shock c, strid voltage electric shock d, contact voltage electric shock
48. Under different environmental conditions, the following safety voltages specified in China are (d)
a, AC 220V b, AC 110V c, AC 55V d, AC 36V
49. Under different environmental conditions, the following safety voltages that I have specified are ( abcd )
a, AC 42V b, AC 36V c, AC 12V d, AC 6V
50. DC safety voltage upper limit is (c)
a, 220V b, 110V c, 72V d, 80V
51. What type of low voltage switch is shown in the figure below ( a )
a, knife switch b, iron shell switch c, transfer switch d, low voltage circuit breaker
52. What type of low voltage switch is shown in the figure below ( b )
a, knife switch b, iron shell switch c, transfer switch d, low voltage circuit breaker
53. What type of low voltage switch is included in the figure below ( c )
a, knife switch b, iron shell switch c, transfer switch d, low voltage circuit breaker
54. What type of low voltage switch is shown in the figure below ( d )
a, knife switch b, iron shell switch c, transfer switch d, low voltage circuit breaker
55. The following fuses belong to the low-voltage fuse: (abcd)
a, porcelain plug-in fuse b, spiral fuse c, unfilled tube fuse d, with filler fuse The fuse below is the kind of low-voltage fuse (a)
a, porcelain plug-in fuse b, spiral fuse c, unfilled tube fuse d, with filler fuse
57. The fuse below is the kind of low voltage fuse (b)
a, porcelain plug-in fuse b, spiral fuse c, unfilled tube fuse d, with filler fuse
58. The fuse below is the kind of low voltage fuse (c)
a, porcelain plug-in fuse b, spiral fuse c, unfilled tube fuse d, with filler fuse
59. The fuse below is the kind of low voltage fuse (d)
a, porcelain plug-in fuse b, spiral fuse c, unfilled tube fuse d, with filler fuse
60. The pointer multimeter operation technique is: (c)
1. Carefully check the position of the test leads before measurement
2. According to the measurement object, turn the transfer switch to the corresponding gear position.
3. When reading, read the data according to the measured object at the corresponding scale.
4, measurement
a, 1324 b, 1423 c, 1234 d, 3241
61. Grounding resistance measuring instrument The specific steps of measuring the grounding resistance of the line are: (c)
1. Disconnect the grounding mains from the grounding body or disconnect the grounding points of all the grounding lines on the grounding mains.
2. Install a temporary grounding wire at the disconnected ground wire.
3. Insert the two measuring ground rods into the ground 20m away from the grounding body and 40m away. Both should be inserted vertically into the depth of the ground for 400mm.
4. Place the grounding resistance meter in a flat place near the grounding body and then wire it.
5. After the measurement, remove the insulation resistance meter to measure the wiring, connect the connection point between the grounding trunk and the grounding body, and remove the temporary grounding wire.
a, 13245 b, 23451 c, 12345 d, 52314
62. ETCR2000 clamp type grounding resistance meter operation steps are (c)
1. After pressing the POWER button, the meter is energized and the clamp is in self-test state; at this time, the natural static state of the clamp should be maintained. The clamp should not be turned over. The clamp should not apply any external force in any direction, otherwise the test accuracy will be affected.
2. After the power-on self-test status is over, the night crystal display “OL†can be tested. If “E†is displayed, the self-test is incorrect and cannot enter the test state.
3. Test once with a random test loop. The value displayed at this time should be consistent with the standard value of the test loop.
4, the horizontal hand holding the pliers table, open the jaws, put the tested wire, flat iron, etc. into the jaws, the jaws closed, observe the liquid crystal display.
5. The data recorder records the location and data, and always pays attention to the top of the building to prevent foreign objects from falling and injuring people.
6. After the test is finished, gently open the jaws, remove the clamp, and press the POWER button.
a, 123465 b, 154236 c, 123456 d, 546321
64. The use of DC single-arm bridge is (c)
1. Open the galvanometer lock first, then adjust the zero adjuster so that the pointer is at zero.
2. Connect the measured resistance Rx to the two terminals labeled “Rxâ€. According to the estimated value of the measured resistance, put the measurement magnification of the bridge to the appropriate position and adjust the variable resistance to a certain position. The right place.
3. When measuring, first press the power button “Bâ€, then press the galvanometer button “G†to adjust the variable resistance according to the direction of the galvanometer pointer. If the galvanometer pointer is deflected to “+â€, it indicates that it should be added. Large comparator arm resistance; if the pointer is deflected toward "-", the comparator arm resistance should be reduced. Repeat the adjustment of the arm resistance until the galvanometer is zero and the bridge is fully balanced.
4. At the end of the measurement, the galvanometer button “G†should be released before the power button “B†can be released. If the power button "B" is released first, when measuring the resistance with a large inductance, the self-induced electromotive force will be generated due to the disconnection of the power supply. This electromotive force acts on the galvanometer circuit, causing the galvanometer pointer to collide and damage, even Burn out the coil of the galvanometer. The galvanometer pointer should be locked after the bridge is used.
a, 1324 b, 1432 c, 1234 d, 4321
65. The normal operation of the test for fixed equipment is: (a)
1. When conducting test work on a normal operating fixture, you must contact the driver on duty and explain the driver's precautions during the test. If there is any change, ask the driver to explain clearly.
2. When testing on a normal operating device, the device must be taken out of the normal operating system. The test can only be carried out after the standby device is in normal operation.
3. When testing without backup equipment, before the test, measures must be taken on the equipment system to make the equipment meet the normal operation requirements, in case there is a critical situation after the power failure and shutdown during the test.
4. When testing in an abnormal state, there must be safety technical measures, and the test can only be carried out after approval by the technical person in charge.
5. Mine hoist winch dynamic test After emergency braking, the wire rope must be inspected. When the wire rope meets the requirements, the winch can be put into normal operation.
6. When testing the mine pump, the pump gate should be closed before the pump starts, so that the motor starts in the light load state, then gradually open the gate to increase the motor load.
a, 123456 b, 123654 c, 256314 d, 654321
66. The power outage sequence is (d)
1. The power failure operation of the transformer (distribution) should be carried out by two people. One of them is monitored and operated by one person. According to the content and sequence of the operation of the switch operation, the simulation operation is first performed on the operation simulation board, and the switch device can be operated without any error. .
2. The switch on both sides of the transformer, the power failure operation sequence is to stop the load side and then stop the power supply side; first stop the low voltage, then stop the high voltage.
3. When there is a capacitor device, the capacitor group switch should be stopped first, and then each outlet switch should be stopped.
4. When operating the switchgear, stop the circuit breaker first, then stop the isolating switch. When stopping the circuit breaker, stop the circuit breaker first, then stop the total circuit breaker; when stopping the isolation switch, pull the load side first and then pull the power side.
a, 3214 b, 4321 c, 2314 d, 1234
67. The voltage is below 110kV, the voltage is lower, the transmission power is smaller, the transmission distance is shorter, and the main power is supplied to the local load, which is called local network. With the development of the national economy, the voltage level has gradually reached 220kV. Such grids are: (a)
a, local network b, regional network c, city network d, rural network
68. The voltage of 110kV and above, the voltage is higher, the transmission power is large, the transmission distance is long, and the main power is supplied to the large regional substation, called (b)
a, local network b, regional network c, city network d, rural network
69. The main part of the transformer includes (c).
a, a closed core b, two coils (often called windings)
c, a closed core and two coils d, winding
70. The power transformer can be divided into (b) according to the cooling medium.
a, oil immersed b, oil immersed and dry type c, dry d, special transformer
71. The ratio of the primary and secondary voltages of the single-phase transformer to the turns ratio of the primary and secondary windings is (a).
a, proportional b, inverse ratio c, 1:1 relationship d, uncertain
72. The ratio of the primary and secondary currents of the single-phase transformer to the turns ratio of the primary and secondary windings is (b).
a, proportional b, inverse ratio c, 1:1 relationship d, uncertain
73. The iron core of the power transformer is composed of (b) two parts.
a, core column b, core column and iron yoke c, iron yoke d, winding
74. The structure of the transformer core is generally divided into two categories: (d).
a, heart b, shell c, winding d, heart and shell
75. The power transformer adjusts the voltage by setting a tap on one of the side windings and changing (d) to achieve a stepwise adjustment of the voltage ratio.
a, current b, voltage c, winding d, number of turns of the winding
76. The temperature of each component is different when the transformer is running, and (c) the temperature is the highest.
a, core b, transformer oil c, winding d, outer casing
77. In order to facilitate monitoring the temperature of various components of the transformer during operation, (a) is specified as the allowable temperature.
a, upper oil temperature b, core temperature c, winding temperature d, case temperature
78. Parallel operation of the transformer is to connect the primary side and secondary side windings of two or more transformers to (a) and supply power to the load.
a, common bus b, two coils c, neutral point d, winding
79. The isolating switch has no special structure (c), and it is not allowed to use it to carry out the pulling or closing operation.
a, core b, neutral point c, arc extinguishing device d, winding
80. The operation sequence when the isolating switch and the circuit breaker are closed is (b):
a, first cut off the load circuit with a circuit breaker, then disconnect the isolating switch
b. Close the isolation switch first, then connect the load circuit with a circuit breaker.
c. At the same time as the isolating switch is closed, the load circuit is connected by a circuit breaker.
d, the above are all wrong
81. The operation sequence when the isolating switch and the circuit breaker are opened is (a):
a, first cut off the load circuit with a circuit breaker, then disconnect the isolating switch
b. Close the isolation switch first, then connect the load circuit with a circuit breaker.
c. At the same time as the isolating switch is closed, the load circuit is connected by a circuit breaker.
d, the above are all wrong
82. Vacuum circuit breaker refers to (c) a circuit breaker that divides and combines circuits in a high vacuum.
a, isolation switch b, core c, contact d, winding
83. The high voltage circuit breaker is a special electrical appliance for the high voltage circuit under normal or fault conditions.
a, turn on b, turn on or off c, turn off d, all of the above are wrong
84. The main part of the vacuum circuit breaker is a vacuum interrupter, which is composed of (d) and other parts.
a, moving contact and static contact b, static contact and shield
c, moving contact, static contact, shield d, moving contact, static contact, shield, insulating shell
85. Sulfur hexafluoride circuit breaker is a high voltage circuit breaker that uses (d) gas as insulation and arc extinguishing medium.
a, SF2 b, SF3 c, SF5 d, SF6
86. A power device consisting of multiple high-voltage switchgears installed in a power plant, substation or power distribution station is called (a).
a, complete power distribution device b, control device c, power distribution device d, substation
87. Insufficient reactive power will cause (c), thus damaging the electrical equipment, which will seriously cause the grid to collapse, causing the system to collapse and causing large-scale power outages.
a, the system voltage rises b, the system power decreases
c, system voltage decreases d, system current decreases
88. The direct function of the phase shifting capacitor is to increase the line (d) in parallel on the line.
a, current size b, voltage size c, power level d, power factor
89. The ambient temperature of the capacitor should not exceed (c).
a, 20 ° C b, 30 ° C c, 40 ° C d, 50 ° C
90. The relative humidity of the air around the environment where the capacitor is located should not be greater than (d).
a, 50% b, 60% c, 70% d, 80%
91. The altitude of the environment where the capacitor is located should not exceed (b).
a, 900m b, 1000m c, 1100m d, 1200m
92. High-voltage capacitors with a total oil quantity (a) or higher shall be installed in a separate explosion-proof room.
a, 300kg b, 400kg c, 500kg d, 600kg
93, high voltage capacitors can use (b) as the discharge load;
a, the low voltage winding b of the voltage transformer, the high voltage winding of the voltage transformer
c, lighting equipment d, electric motor
94. The internal three-phase capacitor is (c) when the rated voltage of the delta connection capacitor matches the line voltage.
a, series b, parallel c, delta connection d, star connection
95. The internal three-phase capacitor is (d) when the rated voltage of the delta connection capacitor matches the line phase voltage.
a, series b, parallel c, delta connection d, star connection
96. The current in the capacitor operation should not exceed (c) times the rated current of the capacitor for a long time.
a, 1.1 b, 1.2 c, 1.3 d, 1.4
97. Under normal circumstances, the parallel capacitor should be put into or out according to the height of the line (d) and the level of the voltage.
a, current size b, voltage size c, power level d, power factor
98. When the power factor is lower than (a) and the voltage is low, the capacitor bank should be put into operation.
a, 0.9 b, 0.8 c, 0.7 d, 0.6
99. When the power factor approaches 1 and there is a leading trend, (b) should exit the capacitor bank.
a, the current is high b, the voltage is high c, the current is low d, the voltage is low
100. When the total capacity of the high voltage capacitor bank does not exceed 100kvar, (b) is available.
a, load switch protection and control
b, fall fuse protection and control
c, vacuum circuit breaker or other circuit breaker protection and control
d, AC contactor, knife switch, fuse or knife fuse switch protection and control
101. When the total capacity is 100~300kvar, (a) should be adopted.
a, load switch protection and control
b, fall fuse protection and control
c, vacuum circuit breaker or other circuit breaker protection and control
d, AC contactor, knife switch, fuse or knife fuse switch protection and control
102. When the total capacity is above 300kvar, (c) should be used.
a, load switch protection and control
b, fall fuse protection and control
c, vacuum circuit breaker or other circuit breaker protection and control
d, AC contactor, knife switch, fuse or knife fuse switch protection and control
103. When the total capacity of the low-voltage capacitor bank does not exceed 100kvar, (d) is available.
a, load switch protection and control
b, fall fuse protection and control
c, vacuum circuit breaker or other circuit breaker protection and control
d, AC contactor, knife switch, fuse or knife fuse switch protection and control
104. When the total capacity is above 100kvar, (d) should be used.
a, load switch protection and control
b, fall fuse protection and control
c, vacuum circuit breaker or other circuit breaker protection and control
d, low voltage circuit breaker protection and control
105. The 10kV power capacitor without fuse inside should be protected by the fuse of the stage. The fuse current should be selected according to the rated current of the capacitor (c).
a, 0.5~1 times b, 1.0~1.5 times c, 1.5~2 times d, 2~2.5 times
106. Under normal circumstances, when the whole station is powered off, it should be (a).
a, first open the switch of the capacitor, then pull open the switch of each line
b. First close the switch of each line, then close the switch of the capacitor line
c. Close the switch of each line and close the switch of the capacitor line.
d, the above are all wrong
107. Under normal circumstances, when the whole station resumes power transmission, it should be (b).
a, first open the switch of the capacitor, then pull open the switch of each line
b. First close the switch of each line, then close the switch of the capacitor line
c. Close the switch of each line and close the switch of the capacitor line.
d, the above are all wrong
108. In order to check and repair, after the capacitor is disconnected from the power supply, the worker must use (b) for manual discharge before the worker approaches, regardless of whether the capacitor is equipped with a discharge device.
a, lighting equipment b, portable special discharge load
c, motor d, reactor
109. The static dynamic reactive power compensation device is abbreviated as (d).
a, SUC b, SVB c, SUB d, SVC
110, SVC working principle description The correct formula is: (b)
a, QN = QV + QC + QTCR = constant (or 0)
b, QN = QV - QC + QTCR = constant (or 0)
c, QN = QV - QC - QTCR = constant (or 0)
d, QN = QV - QC = constant (or 0)
111. Articles 443 and 457 of the “Safety Regulations for Coal Mines†stipulate that underground distribution transformers ( d ) are strictly prohibited.
a, the neutral point is not grounded b, the neutral point is grounded by the arc suppression coil
c. The neutral point is grounded directly through the resistor d and the neutral point.
112. Mine high voltage power grid, measures must be taken to limit the single-phase grounding capacitor current not to exceed (b).
a, 10A b, 20A c, 30A d, 40A
113. In the power system, the generator and transformer (as the power source) are connected to the common end of the star connection (a).
a, neutral point b, control device c, power distribution device d, substation
114. In general, the relay protection device consists of (d).
a, measurement part b, logic part c, execution part d, measurement part, logic part and execution part
115. A normal valve type arrester means (c).
a, magnetic blow valve type arrester b, metal oxide valve type arrester
c, silicon carbide valve arrester d, the above are wrong
116. The silicon carbide valve arrester is mainly composed of a plurality of spark gaps and a corundum valve resistance disc (a).
a, series b, parallel c, delta connection d, star connection
117. Ordinary valve type arrester has sufficient insulation strength to the ground due to the spark gap group, during normal operation (b).
a, will be broken down by the power frequency voltage b, will not be broken down by the power frequency voltage
c, will not be broken by high voltage d, the above are wrong
118. The main working element of the metal oxide arrester is (d).
a, linear resistor b, nonlinear resistor
c, metal varistor sheet d, metal oxide varistor
119. The power supply used in substation switch control, relay protection, automatic devices and signal equipment is called (c).
a, AC operating power b, DC operating power
c, operating power supply d, regulated power supply
120, operating power can be divided into ( c ):
a, AC operating power b, DC operating power
c, AC operating power and DC operating power d, the above are wrong
121. For small-capacity substations with relatively simple wiring methods, (a) is often used.
a, AC operating power b, DC operating power
c, AC operating power and DC operating power d, the above are wrong
122. For a substation that is more important and has a larger capacity, it is generally powered by a battery (b).
a, AC operating power b, DC operating power
c, AC operating power and DC operating power d, the above are wrong
123. The basic requirement for operating the power supply is to have enough (d).
a, accuracy b, stability c, rapidity d, reliability
124. From the basic structure and working principle, the transformer is a kind of (b).
a, capacitor b, transformer c, reactor d, special transformer
125, GL series inductive overcurrent relay has both (a) inductive components.
a, inverse time characteristic b, time limit characteristic c, volt-ampere characteristic d, above are all wrong
126. When technical measures to prevent personal electric shock are not used, (c).
a, water can not be used for fire extinguishing b, water can be used for live fire
c, water can not be used for live fire extinguishing d, the above are wrong
127. Dry sand is especially suitable for (c).
a, with electric fire extinguishing b, put out various fires
c. Extinguish the fires of oils and other flammable liquids. D. The above are all wrong. 2. Multiple choice questions.
1. Electrical power related to those parameters (abc)
a, the voltage at both ends of the circuit, the current intensity in the circuit
c, the power-on time is proportional to d, the voltage in the circuit
2. AC power means that the direction and size are periodically changed with time ( abc )
a, current b, electromotive force c, voltage d, electrical work
3. Sinusoidal alternating current means that the direction and size change sinusoidally with time (abc)
a, current b, electromotive force c, voltage d, electric power
4. The following colors are safe colors ( abcd )
a, red b, blue c, yellow d, green
5. The following types of signs are safety signs ( abcd )
a, prohibition mark b, warning sign c, instruction mark d, prompt sign
6. The electrical load is usually divided into the following categories (abc).
a, one type of load b, two types of load c, three types of load d, four types of load
7. The following "five-proof" functions of the high-voltage switchgear are: (abcd)
a, to prevent the load pull (close) isolation switch b, to prevent mis-separation (closed) circuit breaker
c. Prevent the grounding wire d from being charged and prevent the grounding switch from being connected
8. When encountering thunderstorms, pay attention to safety (abcd)
a. It is not suitable to enter temporary shacks, guard posts and other buildings without lightning protection facilities.
b. It is not advisable to hide under the big trees to avoid rain. If you have to stay under the big tree, you must keep the distance between the tree and the branches for more than two meters. You should kneel as much as possible and close your feet together.
c. It is not advisable to use communication appliances (wireless phones, walkie-talkies, radios, televisions, etc.), and the power should be turned off and the antenna disconnected.
d. It is not advisable to raise objects such as umbrellas, shovel, fishing rods and ball pythons in the wilderness. People who are outdoors can return to the house as soon as possible. When thunder and lightning, the windows should be closed. Sometimes some fireballs (ball-like thunder) can break through the window.
9. The main measures to prevent lightning damage to the power supply system are: ( abcd )
a, substation incoming line protection
b. Install the valve type arrester on the busbar of the substation
c. Install the valve type arrester at the neutral point of the main transformer
d. Install a valve type arrester at the terminal of the power cable directly connected to the overhead line.
10. The basic types of short circuits in three-phase power systems are: ( abcd )
a, three-phase short circuit b, two-phase short circuit c, two-phase ground short circuit d, single-phase short circuit
11. The hazard of short circuit current is (abcd)
a. When the short-circuit current passes through the electrical equipment, it will cause serious heat generation of the conductor, causing the temperature of the conductor to rise or even melt, and the insulation may be damaged;
b. A large amount of electric power is generated between the phases to act on the conductor, which may cause deformation or damage of the device.
c. There is often an arc generated in the short circuit. The high temperature arc will burn the faulty equipment or burn people around, and even cause fire.
d. When the short-circuit current passes through impedance components such as transformers and lines, a large voltage drop will occur, which will also cause the voltage at the generator terminal to decrease, thus affecting the normal power supply of the power system.
12. The measures and methods for accelerating the arc extinguishing in the switchgear are as follows: (abcd)
a, the gas longitudinally blows the arc b, the gas laterally blows the arc c, the elongated arc d, the arc is in contact with the solid medium
13. Hazards of overvoltage to the safe operation of the power system: (abcd)
a, lightning strikes will cause casualties
b, not only interrupt the power supply
c, causing fire
d, power line and electrical equipment insulation breakdown damage
14. Lightning overvoltage is related to meteorological conditions and is caused by external causes, so it is also called atmospheric overvoltage or external overvoltage. Its form is divided into ( abcd )
a, direct lightning strike voltage b, lightning strike counter overvoltage
c, inductive lightning overvoltage d, lightning intrusion wave
15 of the following forms are internal overvoltages ( abc )
a, power frequency overvoltage b, resonant overvoltage
c, operating over voltage d, inductive lightning overvoltage
16. The following electrical injuries are (abc)
a, electric burn b, electric impression c, skin metallization d, heart stop beating
17. The following are electrical injuries ( abcd )
a, contact burn b, arc burn c, electric imprint d, skin metallization
18. The following factors that are responsible for electric shock damage are ( abcd )
a, current intensity and current duration
b, human body resistance
c, acting on the human body voltage
d, current path
19. In electric shock damage, the current is divided into (abc)
a, sense current b, get rid of current c, lethal current d, detection current
20. Human body resistance is determined by the following factors (abcd)
a, contact voltage b, current path c, duration d, contact area
21. The following are the types of electric shocks ( abcd )
a, single-phase electric shock b, two-phase electric shock c, strid voltage electric shock d, contact voltage electric shock
22. Measures to prevent electric shock accidents include ( abcd )
a, insulation and screen protection measures b, using safety voltage c, protective ground d, working ground
23. The protective earthing and working grounding of electrical equipment are to ensure personal safety. In order to make the safety grounding work properly, the following problems should be noted (abcd)
a. Control the grounding resistance within the allowable range. For example, the grounding resistance of low-voltage electrical equipment and transformers is not more than 4Ω; when the total capacity of the transformer is not more than 100kVA, the grounding resistance is not more than 10Ω.
b. The N-line main line is not allowed to be equipped with switches or fuses.
c. The N lines of each device are not allowed to be connected in series, and should be directly connected to the N lines.
d. In the low-voltage power distribution system, the hole of the N-pin socket connected to the N-line of the power supply is not connected with the hole of the PE line, otherwise the metal casing of the equipment will be charged; if the N-line and the phase line are reversed, Bring dangerous voltage to the enclosure.
24. Which of the following equipment and components in the power distribution system require grounding protection ( abcd )
a metal casing or foundation for motors, transformers, circuit breakers and other electrical equipment;
b. Transmission of electrical equipment;
c, the secondary winding of the transformer;
d. Metal or reinforced concrete frame of the distribution equipment inside and outside the house;
25.按照《煤矿安全规程》ã€ã€Šç”µä¸šå®‰å…¨å·¥ä½œè§„程》ç‰æœ‰å…³è§„定,防触电安全措施包括:( abcd )
aã€å¿…é¡»ç»è¿‡ä¸“业培è®ï¼Œè€ƒè¯•åˆæ ¼ï¼ŒæŒæœ‰æ•ˆè¯ä»¶ä¸Šå²—。
bã€å…·æœ‰ä¸€å®šçš„电气ç†è®ºçŸ¥è¯†å’Œç”µå·¥åŸºç¡€çŸ¥è¯†ï¼Œäº†è§£ç”µæ°”设备的性能ã€ç»“构原ç†å’Œä¿æŠ¤è£…置的è¿è¡Œæƒ…况,掌æ¡æ£€ä¿®ã€è¯•éªŒã€ç»´æŠ¤æŠ€æœ¯ï¼Œç†Ÿæ‚‰è´¨é‡æ ‡å‡†ã€å®‰å…¨æŠ€æœ¯è¦æ±‚åŠå…¶ä»–æœ‰å…³è§„ç¨‹å’Œæ ‡å‡†ã€‚
cã€ç†Ÿæ‚‰ç»´ä¿®èŒƒå›´å†…的供电系统ã€ç”µæ°”设备和电缆线路的主è¦æŠ€æœ¯ç‰¹å¾ï¼Œä»¥åŠç”µç¼†çš„分布情况。
dã€æ‰€æœ‰åœé€ç”µå·¥ä½œï¼Œå¿…é¡»ä¸¥æ ¼ç¨‹åºæ“作,办ç†åœé€ç”µå·¥ä½œç¥¨ï¼Œé™¤å·¥ä½œè´Ÿè´£äººå¤–,严ç¦æ— 票åœé€ç”µæˆ–约时åœé€ç”µã€‚
26.低压é…电电器包括( abcd )
aã€åˆ€å¼€å…³bã€è½¬æ¢å¼€å…³cã€ç†”æ–器dã€æ–路器
27.低压控制电器包括:( abcd )
aã€æŽ¥è§¦å™¨bã€æŽ§åˆ¶ç»§ç”µå™¨cã€å¯åŠ¨å™¨dã€æŽ§åˆ¶å™¨
29.低压开关的用途包括:( abcd )
aã€éš”离bã€è½¬æ¢cã€æŽ¥é€šç”µè·¯dã€åˆ†æ–电路
30.以下属于低压开关的是:( abcd )
aã€åˆ€å¼€å…³bã€é“壳开关cã€è½¬æ¢å¼€å…³dã€ä½ŽåŽ‹æ–路器
31.下列继电器属于常用继电器的有:( abcd )
aã€çƒç»§ç”µå™¨bã€ä¸é—´ç»§ç”µå™¨cã€ç”µæµç»§ç”µå™¨dã€ç”µåŽ‹ç»§ç”µå™¨ã€é€Ÿåº¦ç»§ç”µå™¨ã€ç‰ç‰ã€‚
32.下列继电器属于常用继电器的有:( abcd )
aã€çƒç»§ç”µå™¨bã€ä¸é—´ç»§ç”µå™¨cã€ç”µæµç»§ç”µå™¨dã€é€Ÿåº¦ç»§ç”µå™¨
33.下列继电器属于常用继电器的有:( abcd )
aã€çƒç»§ç”µå™¨bã€åŽ‹åŠ›ç»§ç”µå™¨cã€ç”µæµç»§ç”µå™¨dã€é€Ÿåº¦ç»§ç”µå™¨
34.以下那些ç§ç±»å±žäºŽæ—¶é—´ç»§ç”µå™¨ï¼ˆ abcd )
aã€ç”µç£å¼bã€ç”µåŠ¨å¼cã€ç©ºæ°”阻尼å¼dã€æ™¶ä½“管å¼
35.三相异æ¥ç”µåŠ¨æœºåœ¨ç…¤çŸ¿ä¸ä¸»è¦åº”用于:( abcd )
aã€é‡‡ç…¤å·¥ä½œé¢bã€æŽ˜è¿›å·¥ä½œé¢cã€äº•ä¸‹é€šé£Ždã€æŽ’æ°´
36.指针å¼ä¸‡ç”¨è¡¨åº”注æ„那些事项:( abcd )
aã€é€‰æ‹©é€‚当的å€çŽ‡æ¡£ï¼Œä½¿æŒ‡é’ˆå°½é‡æŽ¥è¿‘æ ‡åº¦å°ºçš„ä¸å¿ƒéƒ¨åˆ†ï¼Œä»¥ç¡®ä¿è¯»æ•°æ¯”较准确;
bã€æµ‹é‡ç”µé˜»ä¹‹å‰ï¼Œæˆ–è°ƒæ¢ä¸åŒå€çŽ‡æ¡£åŽï¼Œéƒ½åº”将两表笔çŸæŽ¥ï¼Œç”¨å‡‹é›¶æ—‹é’®è°ƒé›¶ï¼Œè°ƒä¸åˆ°é›¶ä½æ—¶åº”æ›´æ¢ç”µæ± ï¼›
cã€æµ‹é‡å®Œæ¯•ï¼Œåº”将转æ¢å¼€å…³æ‹¨åˆ°äº¤æµç”µåŽ‹æœ€é«˜æ¡£ä¸Šæˆ–空档上,以防æ¢è¡¨ç¬”çŸæŽ¥ï¼Œé€ æˆç”µæ± çŸè·¯æ”¾ç”µï¼›
dã€ä¸¥ç¦ç”¨ä¸‡ç”¨è¡¨çš„电阻档直接测é‡å¾®å®‰è¡¨ã€æ£€æµè®¡ã€æ ‡å‡†ç”µæ± ç‰ç±»ä»ªå™¨ä»ªè¡¨çš„内阻。
37.接地电阻测é‡ä»ªè¡¨ä½¿ç”¨æ³¨æ„事项包括:( abcd )
aã€æµ‹é‡å‰åº”将接地装置与被ä¿æŠ¤çš„电气设备æ–开,ä¸å‡†å¸¦ç”µæµ‹è¯•æŽ¥åœ°ç”µé˜»ã€‚
bã€æµ‹é‡å‰ä»ªè¡¨åº”水平放置,然åŽè°ƒé›¶ã€‚
cã€æŽ¥åœ°ç”µé˜»æµ‹é‡ä»ªä¸å‡†å¼€è·¯æ‘‡åŠ¨æ‰‹æŠŠï¼Œå¦åˆ™å°†æŸå仪表。
dã€å°†å€çŽ‡å¼€å…³æ”¾åœ¨æœ€å¤§å€çŽ‡æ¡£ï¼ŒæŒ‰ç…§è¦æ±‚调整å†è®¡ç®—得出接地电阻值
38.高压验电器æ“作技法包括:( abcd )
aã€ä½¿ç”¨é«˜åŽ‹éªŒç”µå™¨éªŒç”µå‰ï¼Œåº”戴ç»ç¼˜æ‰‹å¥—,并使用相应电压ç‰çº§çš„验电器。确定有电æºå¤„实验,确ä¿éªŒç”µå™¨å®Œå¥½
bã€ä½¿ç”¨æ—¶è¦ç‰¹åˆ«æ³¨æ„手æ¡éƒ¨ä½ä¸èƒ½è¶…过护环。
cã€åœ¨è¯æ˜ŽéªŒç”µå™¨ç¡®å®žå®Œå¥½åŽï¼Œåº”将验电器的金属钩é€æ¸é 近被测高压线,直至氖管窗å‘光。
dã€åªæœ‰æ°–管ä¸äº®æ—¶ï¼Œç¡®è®¤æ— 电åŽæ‰å¯ä¸Žè¢«æµ‹ç‰©ä½“直接接触。
39.下列属于高处作业æ“作技法的是:( abcd )
aã€é«˜ç©ºä½œä¸šå¿…é¡»é…戴åˆæ ¼çš„安全带,安全带必须å¯é çš„æ “åœ¨ç‰¢å›ºçš„ç‰©ä½“ä¸Šï¼Œè¿™ä¸ªç‰©ä½“ä¸Žäººç«™ç«‹çš„åœ°ç‚¹ä¹‹é—´ä¸è®¸å˜åœ¨ç›¸å¯¹è¿åŠ¨çš„å¯èƒ½æ€§ã€‚
bã€ä½œä¸šç”¨å…·å¿…须牢固å¯é ,作业用的构架ã€ç«‹æŸ±å’Œè·³æ¿å¿…é¡»å¯é 固定。
cã€é£ŽåŠ›å…级以上或雷雨天气时,ç¦æ¢åœ¨éœ²å¤©é«˜å¤„作业。é‡å†°é›ªæ—¶ï¼Œåº”有防滑措施。
dã€æ— å¯é 的防范措施,ä¸å‡†åœ¨åŒä¸€ç©ºé—´çš„上下层åŒæ—¶ä½œä¸šã€‚
40.撬时的æ“作安全规范包括:( abcd )
a.ä¸å¾—ä½¿ç”¨ç –å¤´ã€çŸ¸çŸ³æˆ–易碎物å“åšæ”¯ç‚¹ã€‚
b.ä¸èƒ½ä½¿ç”¨æœ¨æ¿çš®åšæ’¬æ 。
c.æ“作人员必须选择åˆé€‚çš„ç«™ä½ã€‚
d.两人或两人以上æ“作时,动作必须å调一致,相互照应。
41.磨时的æ“作安全规范包括:( abcd )
a.ä¸å¾—ä½¿ç”¨ç –å¤´ã€çŸ¸çŸ³æˆ–易碎物å“åšæ”¯ç‚¹ï¼›
b.ä¸èƒ½ä½¿ç”¨æœ¨æ¿çš®åšæ’¬æ 。
c.æ“作人员必须选择åˆé€‚çš„ç«™ä½ã€‚
d.两人或两人以上æ“作时,动作必须å调一致,相互照应。
42.拔时的安全规范包括:( abcd )
a.æ’¬æ æ’入深度è¦é€‚当,ä¸èƒ½ä¸€æ¬¡æ’入过深;
b.æ’¬æ 必须有足够的强度。
C.æ“作人员必须选择åˆé€‚çš„ç«™ä½ã€‚
d.两人或两人以上æ“作时,动作必须å调一致,相互照应。
43.顶和è½æ—¶çš„æ“作规范包括:( abcd )
a.å°†åƒæ–¤é¡¶å®‰æ”¾åœ¨é‡ç‰©ä¸‹é¢çš„适当ä½ç½®ã€‚
b.æ“作åƒæ–¤é¡¶ï¼Œå°†é‡ç‰©é¡¶èµ·ã€‚
c.在é‡ç‰©ä¸‹åž«è¿›æž•æœ¨åž›ï¼Œå¹¶è½ä¸‹åƒæ–¤é¡¶ã€‚
d.垫高åƒæ–¤é¡¶ï¼Œå‡†å¤‡å†é¡¶å‡ã€‚
44.顶和è½æ—¶çš„æ“作安全规范包括:( abcd )
a.在使用åƒæ–¤é¡¶å‰ï¼Œåº”当检查和试验åƒæ–¤é¡¶ã€‚
b.åƒæ–¤é¡¶åº•åº§åº”垫平找æ£ï¼Œåº•åº§åŠé¡¶éƒ¨å¿…须用木æ¿æˆ–枕木垫好。ä¸å¾—用é“æ¿ç‰æ˜“滑æ料。
c.å‡èµ·é‡ç‰©æ—¶ï¼Œåº”在é‡ç‰©ä¸‹éšèµ·éšåž«ï¼Œé¡¶é‡ç‰©çš„过程ä¸ï¼Œåƒæ–¤é¡¶åº”å¹³æ£ç›´ç«‹ï¼Œä¸å¾—æªæ–œï¼Œé˜²æ¢å€¾å€’。
d.在使用油压åƒæ–¤é¡¶è½ä¸‹é‡ç‰©æ—¶ï¼Œä¸ºé˜²æ¢ä¸‹è½é€Ÿåº¦è¿‡å¿«å‘生å±é™©ï¼Œè¦åœ¨æ‹†åŽ»æž•æœ¨åŽï¼ŒåŠæ—¶æ”¾å…¥ä¸åŒåŽšåº¦çš„垫木,使é‡ç‰©ç¦»åž«æœ¨çš„è·ç¦»ä¿æŒåœ¨5cm以内,一é¢è½ä¸‹é‡ç‰©ï¼Œä¸€é¢æ‹†åŽ»å’Œæ›´æ¢åž«æœ¨ã€‚
45.采用滚时的安全æ“作规范包括:( abcd )
aã€æ»šç§»é‡é‡å¾ˆå¤§çš„物体时,上下滚é“å¯é‡‡ç”¨é’¢è½¨åˆ¶æˆã€‚滚æ ç”¨æ— ç¼é’¢ç®¡æˆ–圆钢。滚æ 的长度应比下滚é“宽度长20-40cm。
bã€æ»šæ çš„ç›´å¾„ï¼Œæ ¹æ®è·è½½ä¸åŒï¼Œä¸€èˆ¬ä¸º5-10cm。
cã€æ»šè¿é‡ç‰©æ—¶ï¼Œé‡ç‰©çš„å‰è¿›æ–¹å‘用滚æ 在滚é“上的排放方å‘控制。
dã€è¦ä½¿é‡ç‰©ç›´çº¿å‰è¿›å¿…须使滚æ 与滚é“åž‚ç›´ï¼›è¦ä½¿é‡ç‰©æ‹å¼¯ï¼Œåˆ™ä½¿æ»šæ å‘需æ‹å¼¯çš„æ–¹å‘åè½¬ã€‚çº æ£æ»šæ çš„æ–¹å‘,å¯ç”¨å¤§é”¤æ•²å‡»ã€‚
46.èµ·é‡å’Œè¿æ¬å·¥ä½œä¸å®‰å…¨æ³¨æ„事项包括:(abcd)
aã€æœºå…·ä¸è¶…载。事先应估计é‡ç‰©çš„é‡é‡ï¼Œå¿…须在机具å…许的负è·ä»¥ä¸‹ã€‚
bã€å‡†å¤‡å’Œæ£€æŸ¥æœºå…·ã€‚所有机具都必须在工作å‰ä»”细检查,确认安全å¯é æ‰å…许工作。
cã€å‡†å¤‡æ”¾ç½®åœ°ç‚¹ã€‚事先确定放置地点,清ç†å‡ºç‰©ä½“放置和人员æ“作的必须空间,准备好承垫用的物å“。
dã€æ£€æŸ¥è¿æ¬è·¯çº¿ã€‚清除通é“上的障ç¢ï¼Œä¿è¯é‡ç‰©å’Œäººå‘˜é¡ºåˆ©é€šè¿‡ã€‚
47.电气设备检修ã€è¯•éªŒå·¥æ“作时的安全规定包括:( abcd )
aã€å¿…须有2å以上的人员从事检修ã€è¯•éªŒå·¥ä½œã€‚
b〠çå‰ä¸å‡†å–酒,上çæ—¶ä¸åšä¸Žæœ¬èŒå·¥ä½œæ— å…³çš„äº‹æƒ…ï¼Œä¸¥æ ¼éµå®ˆæ“作的相关规定。工作ä¸ï¼Œä¸¥è‚ƒè®¤çœŸã€é›†ä¸ç²¾åŠ›ï¼Œä¸¥æ ¼æ‰§è¡Œåœé€ç”µã€éªŒç”µã€æ”¾ç”µç‰æœ‰å…³è§„ç« åˆ¶åº¦ã€‚
cã€éœ€è¿›è¡Œå€’é—¸æ“作时,由å˜(é…)电所的值ç人员按倒闸æ“作规定的顺åºå’Œå®‰å…¨è¦æ±‚进行。
dã€ä¸¥ç¦å¸¦ç”µä½œä¸šï¼Œæ£€ä¿®å·¥åœ¨è·ç¦»å¸¦ç”µä½“较近或在å±é™©åœ°ç‚¹å·¥ä½œæ—¶ï¼Œåº”采å–å¯é 的隔离措施,并设专人监护,å¦åˆ™å·¥ä½œäººå‘˜æœ‰æƒæ‹’ç»æ‰§è¡Œå·¥ä½œå‘½ä»¤ã€‚
48.电气设备检修ã€è¯•éªŒå·¥æ“作时的安全规定包括:( abcd )
aã€åœ¨è¿›è¡Œé«˜åŽ‹æ•…障修ç†æˆ–高压试验时,工作场所必须用é®æ 挡ä½ï¼Œå¹¶æ‚¬æŒ‚“高压å±é™©â€è¦ç¤ºç‰Œã€‚
bã€åœ¨æŽ§åˆ¶ç›˜å’Œä¿æŠ¤ç›˜ä¸Šå·¥ä½œæ—¶ï¼Œå¿…须将工作盘和两侧è¿è¡Œç›˜ç”¨å¸ƒå¹”ç‰åŠ 以明显隔开。对新型继电器åŠç»§ç”µä¿æŠ¤è£…置,必须有åˆæ³•è¯ä»¶ï¼Œå¦åˆ™ä¸å‡†æŠ•å…¥ä½¿ç”¨å’Œè¿è¡Œã€‚
cã€åœ¨å›žè·¯ä¸Šå·¥ä½œæ—¶ï¼Œå¿…须切æ–一切å¯ä»¥åé€ç”µçš„电æºï¼Œä¸¥ç¦å¸¦ç”µä½œä¸šã€‚
dã€åœ¨è¿›è¡Œé’»å”ç‰æŒ¯åŠ¨è¾ƒå¤§çš„工作时,应采å–防æ¢è¿è¡Œä¸ä»ªè¡¨è¯¯åŠ¨å’Œé˜²æ¢è¿è¡Œä¸è®¾å¤‡æŽ‰é—¸çš„措施,必è¦æ—¶ç»å€¼ç调度员或值ç负责人åŒæ„,å¯å°†ä¿æŠ¤è£…置暂时退出è¿è¡Œã€‚
49..åœç”µæ³¨æ„事项包括:(abcd)
aã€è®¾å¤‡åœç”µï¼Œå¿…须把å„æ–¹é¢çš„电æºæ–开,且å„æ–¹é¢è‡³å°‘有一个明显æ–开点。
bã€ä¸ºäº†é˜²æ¢æœ‰è¿”é€ç”µæºçš„å¯èƒ½ï¼Œåº”将与åœç”µè®¾å¤‡æœ‰å…³çš„å˜åŽ‹å™¨ä»Žé«˜ä½ŽåŽ‹ä¸¤ä¾§æ–开,电压互感器一次侧æ–开,å–下电压互感器的一ã€äºŒæ¬¡ä¾§ç†”ä¸ç®¡ã€‚
cã€å¯¹äºŽæŸ±ä¸Šå˜åŽ‹å™¨ï¼Œåº”将高压熔æ–器的熔ä¸ç®¡å–下。
dã€æ‹‰æ–电æºéš”离开关åŽï¼Œå¼€å…³æ“作手柄必须é”ä½ã€‚拉æ–çš„æ–è·¯å™¨æ ¹æ®éœ€è¦å–下æ–路器控制回路的熔ä¸ç®¡ã€‚
50.åœé€ç”µæ“作工作许å¯åŒ…括哪些内容( abcd )
aã€å·¥ä½œè®¸å¯äººåº”负责审查工作票ä¸æ‰€åˆ—的安全措施是å¦æ£ç¡®ã€å®Œå¤‡ï¼Œæ˜¯å¦ç¬¦åˆçŽ°åœºæ¡ä»¶ï¼Œå¹¶å®Œæˆæ–½å·¥çŽ°åœºçš„安全措施。
bã€åœ¨å˜ç”µæ‰€å·¥ä½œæ—¶ï¼Œå·¥ä½œè®¸å¯äººä¼šåŒå·¥ä½œè´Ÿè´£äººæ£€æŸ¥åœ¨åœç”µèŒƒå›´å†…所åšçš„安全措施,并指明邻近带电部ä½ï¼ŒéªŒæ˜Žæ£€ä¿®è®¾å¤‡ç¡®æ— 电压åŽï¼ŒåŒæ–¹åœ¨å·¥ä½œç¥¨ä¸Šç¾å—。
cã€åœ¨å˜(é…)电所出线电缆的å¦ä¸€ç«¯å¤´(或线路上的电缆头)çš„åœç”µå·¥ä½œï¼Œåº”得到é€ç”µç«¯å¤´çš„值ç员或调度员的许å¯åŽï¼Œæ–¹å¯è¿›è¡Œå·¥ä½œã€‚ '
dã€å·¥ä½œè´Ÿè´£äººåŠå·¥ä½œè®¸å¯äººï¼Œä»»ä½•ä¸€æ–¹ä¸å¾—擅自å˜æ›´å®‰å…¨æŽªæ–½åŠå·¥ä½œé¡¹ç›®ï¼Œå·¥ä½œè®¸å¯äººä¸å¾—改å˜æ£€ä¿®è®¾å¤‡çš„è¿è¡ŒæŽ¥çº¿æ–¹å¼ï¼Œå¦‚需改å˜æ—¶ï¼Œåº”事先得到工作负责人的åŒæ„。
51.åœé€ç”µæ“作工作许å¯åŒ…括哪些内容( abcd )
aã€åœ¨çº¿è·¯ä¸Šåœç”µå·¥ä½œæ—¶ï¼Œå·¥ä½œè´Ÿè´£äººåº”得到许å¯äººçš„许å¯ï¼Œæ‹‰å¼€å˜é…电的开关或隔离开关,并åšå¥½å®‰å…¨æŽªæ–½åŽæ–¹å¯è¿›è¡Œå·¥ä½œï¼Œåœ¨ä¸Žåœç”µä½œä¸šçº¿è·¯ç›¸äº¤å‰ã€è·¨è¶Šçš„其他å•ä½çš„带电线路åœç”µæ—¶ï¼Œåº”得到有关å•ä½è®¸å¯äººçš„许å¯ï¼Œå¹¶å®ŒæˆçŽ°åœºçš„安全措施åŽæ–¹å¯å·¥ä½œã€‚
bã€åœ¨å·¥ä½œè¿‡ç¨‹ä¸ï¼Œå½“工作许å¯äººå‘现有è¿å安全工作规程规定时,或拆除æŸäº›å®‰å…¨è®¾æ–½æ—¶ï¼Œåº”ç«‹å³å‘½ä»¤å·¥ä½œäººå‘˜åœæ¢å·¥ä½œï¼Œå¹¶è¿›è¡Œæ›´æ£ã€‚
cã€åœ¨å˜(é…)电所出线电缆的å¦ä¸€ç«¯å¤´(或线路上的电缆头)çš„åœç”µå·¥ä½œï¼Œåº”得到é€ç”µç«¯å¤´çš„值ç员或调度员的许å¯åŽï¼Œæ–¹å¯è¿›è¡Œå·¥ä½œã€‚ '
dã€å·¥ä½œè´Ÿè´£äººåŠå·¥ä½œè®¸å¯äººï¼Œä»»ä½•ä¸€æ–¹ä¸å¾—擅自å˜æ›´å®‰å…¨æŽªæ–½åŠå·¥ä½œé¡¹ç›®ï¼Œå·¥ä½œè®¸å¯äººä¸å¾—改å˜æ£€ä¿®è®¾å¤‡çš„è¿è¡ŒæŽ¥çº¿æ–¹å¼ï¼Œå¦‚需改å˜æ—¶ï¼Œåº”事先得到工作负责人的åŒæ„。
52.åœé€ç”µæ“作工作许å¯åŒ…括哪些内容( abcd )
aã€å·¥ä½œè®¸å¯äººåº”负责审查工作票ä¸æ‰€åˆ—的安全措施是å¦æ£ç¡®ã€å®Œå¤‡ï¼Œæ˜¯å¦ç¬¦åˆçŽ°åœºæ¡ä»¶ï¼Œå¹¶å®Œæˆæ–½å·¥çŽ°åœºçš„安全措施。
bã€åœ¨å˜ç”µæ‰€å·¥ä½œæ—¶ï¼Œå·¥ä½œè®¸å¯äººä¼šåŒå·¥ä½œè´Ÿè´£äººæ£€æŸ¥åœ¨åœç”µèŒƒå›´å†…所åšçš„安全措施,并指明邻近带电部ä½ï¼ŒéªŒæ˜Žæ£€ä¿®è®¾å¤‡ç¡®æ— 电压åŽï¼ŒåŒæ–¹åœ¨å·¥ä½œç¥¨ä¸Šç¾å—。
cã€åœ¨çº¿è·¯ä¸Šåœç”µå·¥ä½œæ—¶ï¼Œå·¥ä½œè´Ÿè´£äººåº”得到许å¯äººçš„许å¯ï¼Œæ‹‰å¼€å˜é…电的开关或隔离开关,并åšå¥½å®‰å…¨æŽªæ–½åŽæ–¹å¯è¿›è¡Œå·¥ä½œï¼Œåœ¨ä¸Žåœç”µä½œä¸šçº¿è·¯ç›¸äº¤å‰ã€è·¨è¶Šçš„其他å•ä½çš„带电线路åœç”µæ—¶ï¼Œåº”得到有关å•ä½è®¸å¯äººçš„许å¯ï¼Œå¹¶å®ŒæˆçŽ°åœºçš„安全措施åŽæ–¹å¯å·¥ä½œã€‚
dã€åœ¨å·¥ä½œè¿‡ç¨‹ä¸ï¼Œå½“工作许å¯äººå‘现有è¿å安全工作规程规定时,或拆除æŸäº›å®‰å…¨è®¾æ–½æ—¶ï¼Œåº”ç«‹å³å‘½ä»¤å·¥ä½œäººå‘˜åœæ¢å·¥ä½œï¼Œå¹¶è¿›è¡Œæ›´æ£ã€‚
53.下列属于åœé€ç”µæ“作监护人的èŒè´£çš„是( abcd )
aã€éƒ¨åˆ†åœç”µå·¥ä½œæ—¶ï¼Œç›‘护人应始终ä¸é—´æ–地监护工作人员的最大活动范围,使其ä¿æŒåœ¨è§„定的安全è·ç¦»å†…工作。
bã€å¸¦ç”µå·¥ä½œæ—¶ï¼Œç›‘护人应监护所有工作人员的活动范围ä¸åº”å°äºŽä¸ŽæŽ¥åœ°éƒ¨ä½çš„安全è·ç¦»ï¼ŒæŸ¥çœ‹å·¥ä½œä½ç½®æ˜¯å¦å®‰å…¨ã€å·¥å…·ä½¿ç”¨ä»¥åŠæ“作方法是å¦æ£ç¡®ç‰ã€‚
cã€è‹¥å‘现æŸäº›å·¥ä½œäººå‘˜ä¸æœ‰ä¸æ£ç¡®çš„动作时,应åŠæ—¶æå‡ºçº æ£ï¼Œå¿…è¦æ—¶ä»¤å…¶åœæ¢å·¥ä½œã€‚
dã€ç›‘护人在执行监护工作ä¸ï¼Œåº”全神贯注ä¸å¾—å…¼åšå…¶ä»–工作,如需离开工作现场时,应å¦è¡ŒæŒ‡æ´¾ç›‘护人,并通知被监护的工作人员。
54.åœé€ç”µæ“作工作终结和é€ç”µåŒ…括:( abcd )
aã€å·¥ä½œç»ˆç»“é€ç”µå‰ï¼Œå·¥ä½œè´Ÿè´£äººåº”对检修设备全é¢è¿›è¡Œè´¨é‡æ£€æŸ¥ã€‚检查设备的检修工艺质é‡åº”符åˆæŠ€æœ¯è¦æ±‚。
bã€åœ¨å˜(é…)电所工作时,工作负责人会åŒå€¼çå‘˜åº”å¯¹è®¾å¤‡è¿›è¡Œæ£€æŸ¥ï¼Œç‰¹åˆ«åº”æ ¸å¯¹éš”ç¦»å¼€å…³ä¸Žæ–路器分ã€åˆä½ç½®çš„实际情况是å¦ä¸Žå·¥ä½œç¥¨ä¸Šå¡«å†™çš„ä½ç½®ç›¸ç¬¦ï¼Œæ ¸å¯¹æ— 误åŽåŒæ–¹åœ¨å·¥ä½œç¥¨ä¸Šç¾å—。
cã€å…¨éƒ¨å·¥ä½œå®Œæ¯•åŽï¼Œå·¥ä½œäººå‘˜åº”清ç†çŽ°åœºã€æ¸…点工具和æ料,ä¸åº”将其é—æ¼åœ¨å·¥ä½œçŽ°åœºå’Œæ£€ä¿®çš„设备上。检查接线是å¦æ£ç¡®ï¼Œæ‹‰ã€åˆè¯•éªŒçš„开关åŠéš”离开关å‡åº”在æ–å¼€ä½ç½®ã€‚
dã€çº¿è·¯å·¥ä½œå®Œæ¯•ï¼Œåº”检查相åºåŠå¼€å…³ã€äº¤å‰è·¨è¶Šçš„è·ç¦»æ˜¯å¦ç¬¦åˆè§„定。
55.åœé€ç”µæ“作工作终结和é€ç”µåŒ…括:( abcd )
aã€å·¥ä½œç»ˆç»“é€ç”µå‰ï¼Œå·¥ä½œè´Ÿè´£äººåº”对检修设备全é¢è¿›è¡Œè´¨é‡æ£€æŸ¥ã€‚检查设备的检修工艺质é‡åº”符åˆæŠ€æœ¯è¦æ±‚。
bã€åœ¨å˜(é…)电所工作时,工作负责人会åŒå€¼çå‘˜åº”å¯¹è®¾å¤‡è¿›è¡Œæ£€æŸ¥ï¼Œç‰¹åˆ«åº”æ ¸å¯¹éš”ç¦»å¼€å…³ä¸Žæ–路器分ã€åˆä½ç½®çš„实际情况是å¦ä¸Žå·¥ä½œç¥¨ä¸Šå¡«å†™çš„ä½ç½®ç›¸ç¬¦ï¼Œæ ¸å¯¹æ— 误åŽåŒæ–¹åœ¨å·¥ä½œç¥¨ä¸Šç¾å—。
cã€ç»ä¸Šè¿°æ£€æŸ¥åŽï¼Œå·¥ä½œè´Ÿè´£äººå†æ¬¡ä»”细对检修设备ã€å·¥ä½œçŽ°åœºè¿›è¡Œæ£€æŸ¥ï¼Œè®¤ä¸ºæ— 问题åŽå®£å¸ƒå·¥ä½œç»ˆç»“。
dã€æ‹†é™¤ä¸´æ—¶åœ°çº¿ã€ä¸´æ—¶é®æ ã€ä¸´æ—¶æ ‡ç¤ºç‰Œï¼Œæ¢å¤å¸¸è®¾é®æ å’Œæ ‡ç¤ºç‰Œã€‚ä¸´æ—¶åœ°çº¿æ‹†é™¤åŽï¼Œå·¥ä½œäººå‘˜ä¸å¾—触åŠæ£€ä¿®çš„设备或线路。
56.下列规程属于电气安全规程的有:( abcd )
aã€ç”µä¸šå®‰å…¨å·¥ä½œè§„程
bã€ç”µä¸šç”Ÿäº§äº‹æ•…调查规程
cã€ç‰¹ç§ä½œä¸šå®‰å…¨å·¥ä½œè§„程
dã€ç”µæ°”设备典型消防规程
57.下列制度属于电气现场管ç†åˆ¶åº¦çš„有:( abcd )
aã€è¿è¡Œç»´æŠ¤åˆ¶åº¦
bã€å·¡è§†æ£€æŸ¥åˆ¶åº¦
cã€ç¼ºé™·ç®¡ç†åˆ¶åº¦
dã€å²—ä½è´£ä»»åˆ¶åº¦
58.电力系统包括:( abcd )
aã€å‘电厂bã€é€å˜ç”µçº¿è·¯cã€ä¾›é…电所dã€ç”¨ç”µå•ä½
59.电网的形å¼åˆ†ä¸ºï¼ˆ abcd )
aã€åœ°æ–¹ç½‘bã€åŒºåŸŸç½‘cã€åŸŽç½‘dã€å†œç½‘
60电力系统è¿è¡Œçš„特点:( abcd )
aã€ç”µèƒ½ç”Ÿäº§ã€è¾“é€å’Œä½¿ç”¨çš„è¿žç»æ€§bã€ä¸Žå›½æ°‘ç»æµŽçš„å„个部门密切相关
cã€ä¸Žäººä»¬çš„生产ã€ç”Ÿæ´»å¯†åˆ‡ç›¸å…³dã€æš‚æ€è¿‡ç¨‹éžå¸¸çŸæš‚
61.对供电系统的基本è¦æ±‚是:( abcd )
aã€ä¾›ç”µå¯é bã€ä¾›ç”µå®‰å…¨cã€ç”µèƒ½è´¨é‡dã€ç»æµŽä¾›ç”µ
62.矿井供电系统由那些组æˆï¼ˆ abcd )
aã€åœ°é¢å˜ç”µæ‰€bã€äº•ä¸‹ä¸å¤®å˜ç”µæ‰€cã€é‡‡åŒºå˜ç”µæ‰€dã€å·¥ä½œé¢å˜ç”µç«™å’Œé…电点
63.å˜ç”µæ‰€åŒ…括那些类型( abcd )
aã€å®¤å¤–å˜ç”µæ‰€bã€å®¤å†…å˜ç”µæ‰€cã€ç§»åŠ¨å¼å˜ç”µæ‰€dã€ç®±å¼å˜ç”µæ‰€
64.å˜ã€é…电所主接线方å¼çš„基本è¦æ±‚( abcd )
aã€ç®€å•ã€å®‰å…¨ã€å¯é ã€é½å…¨ã€‚å°½é‡è¾¾åˆ°ç®€å•ï¼Œä¾›ç”µæ–¹å¼å¯é ,主设备é½å…¨ï¼›
bã€åˆç†ã€ç»æµŽã€çµæ´»ã€‚设备选择åˆç†ï¼Œè¿è¡Œå®‰å…¨ç»æµŽï¼Œè¿è¡Œçµæ´»ï¼Œå¹¶é€‚当考虑未æ¥çš„å‘展;
cã€ä¾¿äºŽç»´æŠ¤ï¼Œæ“作简å•ã€‚便于维护检修,æ“作æ¥éª¤ç®€å•ã€æ–¹ä¾¿ï¼›
dã€å¯¹æ•…障处ç†ï¼Œèƒ½ä¿è¯å®‰å…¨ï¼Œä¾¿äºŽæ‰§è¡Œè§„定的安全措施,年è¿è¡ŒæŸå¤±å°ã€‚
65.架空线路主è¦åŒ…括一下那些部件( abcd )
aã€ç”µæ†bã€æ¨ªæ‹…cã€å¯¼çº¿dã€ç»ç¼˜åç‰
66.电缆敷设原则是( abcd )
aã€æ•·è®¾è·¯å¾„最çŸï¼Œå°½é‡å°‘æ‹å¼¯ï¼›
bã€ä¸å—阳光直晒,散çƒæ¡ä»¶è¦å¥½ã€‚
cã€å°½é‡é¿å¼€ç©¿è¶Šé“è·¯ã€å…¬è·¯ä»¥åŠå…¶ä»–管线ç‰ã€‚
dã€é¿å¼€è§„划ä¸çš„挖土地段。
67.敷设电缆时应注æ„哪些安全问题( abcd )
aã€ä¸ºäº†ä½¿ç”µç¼†ä¸å—挤压和机械æŸä¼¤ï¼Œç”µç¼†å¼•å…¥åŠå¼•å‡ºå»ºç‘物ã€æž„ç‘物ã€æ¥¼æ¿æˆ–墙å£æ—¶åº”穿管敷设,穿管其管内径ä¸èƒ½å°äºŽç”µç¼†å¤–径的1.5å€
bã€ä¸ºäº†ä½¿ç”µç¼†ä¸å—挤压和机械æŸä¼¤ï¼Œç”µç¼†ä¸Žé“è·¯ã€é“路交å‰å¤„应穿管敷设,穿管其管内径ä¸èƒ½å°äºŽç”µç¼†å¤–径的1.5å€
cã€ç”µç¼†ä¸å…许与煤气管路ã€å¤©ç„¶æ°”管路以åŠå…¶ä»–å¯ç‡ƒæ€§æ°”体管路敷设在åŒä¸€æ²Ÿé“ä¸ï¼›
dã€ç”µç¼†çš„金属外皮,å°ç«¯ç›’ã€æŽ¥çº¿ç›’ã€ä¿æŠ¤ç®¡ç‰é‡‘属物å‡åº”接地。
68ã€å˜åŽ‹å™¨çš„主è¦éƒ¨åˆ†åŒ…括( ab )。
aã€ä¸€ä¸ªé—åˆé“芯bã€ä¸¤ä¸ªçº¿åœˆ(常称为绕组)
c ã€æ²¹ç®±d ã€ç»ç¼˜å¥—管
69ã€å˜åŽ‹å™¨æŒ‰ç”¨é€”一般分为( abd )。
aã€ä»ªç”¨äº’感器bã€ç”µåŠ›å˜åŽ‹å™¨c ã€å•ç›¸å˜åŽ‹å™¨d ã€ç‰¹ç§å˜åŽ‹å™¨
70ã€ç”µåŠ›å˜åŽ‹å™¨æŒ‰å†·å´ä»‹è´¨å¯åˆ†ä¸ºï¼ˆ bd )。
aã€æ•´æµå˜åŽ‹å™¨bã€æ²¹æµ¸å¼å˜åŽ‹å™¨c ã€è‡ªè€¦å˜åŽ‹å™¨d ã€å¹²å¼å˜åŽ‹å™¨
71ã€ç”µåŠ›å˜åŽ‹å™¨çš„é“芯是由( ac )两部分组æˆã€‚
aã€é“芯柱bã€åˆ†æŽ¥å¼€å…³c ã€é“è½d ã€ç£é€š
72ã€å˜åŽ‹å™¨é“芯的结构一般分为( ac )两类。
aã€å¿ƒå¼bã€é«˜åŽ‹c ã€å£³å¼d ã€ä½ŽåŽ‹
73ã€ç”µåŠ›å˜åŽ‹å™¨å†…部主è¦ç»ç¼˜æ料有( abcd )。
aã€å˜åŽ‹å™¨æ²¹bã€ç»ç¼˜çº¸æ¿c ã€ç”µç¼†çº¸d ã€çš±çº¹çº¸
74ã€ç”µåŠ›å˜åŽ‹å™¨çš„主è¦å‚数有( abcd )。
aã€é¢å®šå®¹é‡bã€é¢å®šç”µåŽ‹c ã€çŸè·¯ç”µåŽ‹d ã€ç©ºè½½æŸè€—
75ã€å˜åŽ‹å™¨è¿‡è´Ÿè½½èƒ½åŠ›å¯åˆ†ä¸ºï¼ˆ ab )。
aã€æ£å¸¸æƒ…况下的过负载能力bã€äº‹æ•…情况下的过负载能力
cã€çŸè·¯æƒ…况下的过负载能力dã€å¯åŠ¨æƒ…况下的过负载能力
76ã€å˜åŽ‹å™¨å¹¶åˆ—è¿è¡Œçš„目的有( acd )。
a〠æ高供电å¯è¡Œæ€§æ£æ¯”
b〠æ高å˜åŽ‹å™¨è¿è¡Œå®‰å…¨æ€§
c〠å¯ä»¥å‡å°‘总备用容é‡ï¼Œå¹¶å¯éšç€ç”¨ç”µé‡çš„å¢žåŠ åˆ†æ‰¹å¢žåŠ æ–°çš„å˜åŽ‹å™¨
d〠æ高å˜åŽ‹å™¨è¿è¡Œç»æµŽæ€§
77ã€å˜åŽ‹å™¨ç†æƒ³å¹¶åˆ—è¿è¡Œçš„æ¡ä»¶æœ‰ï¼ˆ bcd )。
aã€å˜åŽ‹å™¨çš„è”ç»“ç»„æ ‡å·ç›¸å¼‚bã€å˜åŽ‹å™¨çš„电压比相ç‰(å…许有±5%的差值) cã€å˜åŽ‹å™¨çš„è”ç»“ç»„æ ‡å·ç›¸åŒdã€å˜åŽ‹å™¨çš„阻抗电压uZ相ç‰(å…许有±10%的差值)
78ã€çœŸç©ºæ–路器的主è¦éƒ¨åˆ†æ˜¯çœŸç©ºç弧室,它是由( abcd )ç‰éƒ¨åˆ†ç»„æˆã€‚
aã€åŠ¨è§¦å¤´bã€é™è§¦å¤´cã€å±è”½ç½©dã€ç»ç¼˜å¤–壳
79ã€å…氟化硫æ–路器由( abcd )和æ“作机构ç‰ç»„æˆã€‚
aã€é’¢ç’外壳bã€èŠ¯æŸ±cã€å¼•çº¿ç«¯ådã€æ”¯æŒç»ç¼˜
80ã€å…氟化硫æ–路器检修安全注æ„事项( abcd )。
a〠æ–路器在真空状æ€ä¸‹ä¸å…许进行“åˆâ€ã€â€œåˆ†â€æ“作
b〠æ–è·¯å™¨ä¼ åŠ¨æ‹è‡‚åŠæœºæž„å„è½¬åŠ¨éƒ¨åˆ†åŠ é€‚é‡çš„润滑油
c〠机构在æ£å¸¸æ£€ä¿®æ—¶åº”å°†åˆé—¸å¼¹ç°§æ‰€å‚¨èƒ½é‡é‡Šæ”¾
d〠åªæœ‰å½“输出轴处于分闸ä½ç½®æ—¶æ‰èƒ½è¿›è¡Œåˆé—¸æ“作
81ã€å…氟化硫æ–路器的优点包括( acd )。
aã€åœ¨å¼€æ–å°ç”µæ„Ÿç”µæµåŠç”µå®¹ç”µè·¯æ—¶ä¸ä¼šå‡ºçŽ°è¿‡ç”µåŽ‹bã€é™ä½Žé«˜æ¬¡è°æ³¢
cã€å…许开æ–次数多ã€å¯¿å‘½é•¿ã€æ£€ä¿®å‘¨æœŸé•¿dã€ç弧能力强
82ã€åœ¨ä¸æ€§ç‚¹ä¸æŽ¥åœ°çš„高压电网ä¸ï¼Œå•ç›¸æŽ¥åœ°ç”µå®¹ç”µæµçš„主è¦å±å®³ï¼ˆ abcd )。
a〠产生弧光接地过电压
b〠产生交æµæ‚散电æµ
cã€ é€ æˆæŽ¥åœ°ç‚¹çƒç ´ååŠæŽ¥åœ°ç½‘电压å‡é«˜
d〠产生接地电弧引起瓦斯煤尘爆炸
83ã€ä¸æ€§ç‚¹æŽ¥åœ°æ–¹å¼æœ‰ä»¥ä¸‹å‡ ç§ï¼ˆ abc )。
a〠ä¸æ€§ç‚¹ä¸æŽ¥åœ°bã€ä¸æ€§ç‚¹ç»æ¶ˆå¼§çº¿åœˆæŽ¥åœ°
cã€ä¸æ€§ç‚¹ç›´æŽ¥æŽ¥åœ°dã€ä¸æ€§ç‚¹ç»ç”µé˜»æŽ¥åœ°
84ã€é…电网å•ç›¸æŽ¥åœ°æ•…障特点( abc )。
aã€æ˜“é€ æˆäºŒæ¬¡æ•…éšœbã€æ˜“产生å•ç›¸ç”µå¼§æŽ¥åœ°è¿‡ç”µåŽ‹
cã€æ˜“产生é“ç£è°æŒ¯è¿‡ç”µåŽ‹æ²¹æµ¸å¼dã€æ˜“产生电弧
85ã€é«˜åŽ‹å¼€å…³æŸœä¸»è¦ç”±ï¼ˆ bcd )ç‰éƒ¨åˆ†ç»„æˆã€‚
aã€çº¿åœˆbã€ç”µæµäº’感器cã€ç”µåŽ‹äº’感器dã€æ–路器
86ã€æ— 功功率的主è¦æ¶ˆè€—者是( acd )ç‰ã€‚
aã€æ„Ÿåº”电动机bã€ç”µé˜»cã€å˜åŽ‹å™¨dã€ç”µç„Šæœº
87ã€ç”µåŠ›ç”µå®¹å™¨åŒ…括( abcd )ç‰å¤šç§ç”µå®¹å™¨ã€‚
aã€ç§»ç›¸ç”µå®¹å™¨bã€ä¸²è”电容器cã€è€¦åˆç”µå®¹å™¨dã€åŽ‹ç”µå®¹å™¨
88ã€ç”µå®¹å™¨æ‰€åœ¨çŽ¯å¢ƒæ£ç¡®çš„æ述是( abd )。
a〠温度ä¸åº”超过40℃
b〠周围空气相对湿度ä¸åº”大于80ï¼…
c〠周围空气相对湿度ä¸åº”大于60ï¼…
d〠海拔高度ä¸åº”超过1000m
89ã€é«˜åŽ‹å¼€å…³æŸœåº”具有“五防â€è¿žé”功能是指( abcd )。
a〠防æ¢å¸¦è´Ÿè·æŽ¨æ‹‰æ–路器手车
b〠防æ¢æŽ¥åœ°å¼€å…³å¤„在é—åˆä½ç½®æ—¶å…³åˆæ–路器
c〠防æ¢è¯¯å…¥å¸¦ç”µéš”室和防æ¢åœ¨å¸¦ç”µæ—¶è¯¯åˆæŽ¥åœ°å¼€å…³çš„è”é”功能
d〠防æ¢è¯¯åˆ†åˆæ–路器
90ã€è‡ªåŠ¨è·Ÿè¸ªè¡¥å¿æ¶ˆå¼§çº¿åœˆä½œç”¨ï¼ˆ abcd ):
a〠补å¿ç”µå®¹ç”µæµï¼Œå‡å°‘ç”µç¼†æ”¾ç‚®å‡ çŽ‡
b〠å‡å°‘å½¢æˆç”µå¼§æŽ¥åœ°è¿‡ç”µåŽ‹çš„å‡ çŽ‡
c〠å¯æŠ‘制é“ç£è°æŒ¯è¿‡ç”µåŽ‹
d〠å‡å°ç”µç¼†æŸä¼¤ï¼Œæ高电缆寿命
91ã€ç»§ç”µä¿æŠ¤è£…置的基本任务是( abd )
a〠当å‘生故障时,将故障元件从供电系统ä¸åˆ‡é™¤ã€‚
b〠当出现ä¸æ£å¸¸å·¥ä½œçŠ¶æ€æ—¶ï¼Œç»§ç”µä¿æŠ¤è£…置动作å‘出信å·ï¼Œå‡è´Ÿè·æˆ–跳闸。
cã€
d〠继电ä¿æŠ¤è£…置还å¯ä»¥å’Œä¾›ç”µç³»ç»Ÿçš„自动装置é…åˆï¼Œç¼©çŸåœç”µæ—¶é—´ï¼Œæ高供电系统è¿è¡Œçš„å¯é 性。
92ã€å°ç”µæµæŽ¥åœ°é€‰çº¿åŽŸç†ï¼ˆ abcd )
aã€
ZGAR Vape Pods 1.0
ZGAR electronic cigarette uses high-tech R&D, food grade disposable pods and high-quality raw material. A new design of gradient our disposable vape is impressive.We equip with breathing lights in the vape pen and pods.
Our team has very high requirements for product quality, taste allocation and packaging design. Designers only use Hong Kong designers, e-cigarette liquid only imports from the United States, materials are food grade, and assembly factory wants medical grade without ground workshop.
We offer best price, high quality Pod System Vape,Pods Systems Touch Screen,Empty Pod System, Pod Vape System,Disposable Pod device,Vape Pods to all over the world.
Pods,Vape Pods,Pod Systems,Atomizer, E-cigarette, Empty Pod Vape Manufacturer and Supplier in China
ZGAR INTERNATIONAL TRADING CO., LTD. , https://www.zgarette.com